Specifications
Meter Accuracy
• kWh Better than Class 1 per EN 62053-21 & BS 8431
• Kvarh Better than Class 2 per EN 62053-23 & BS 8431
• kW & kVA Better than Class 0.5 IEC 60688
• kvar Better than Class 0.5 IEC 60688
• Amps & Volts Class 0.2 IEC 60688 (0.01In – 1.2In or 0.1Un – 1.2Un)
• PF ±0.2° (0.05In – 1.2In and 0.2Un – 1.2Un)
• Neutral Current Class 0.5 IEC 60688 (0.05In – 1.2In)
Voltage Inputs
• 20-280 Volts Line To Neutral, 20-480 Volts Line to Line
• Universal Voltage Input • Input Withstand Capability – Meets IEEE C37.90.1 (Surge Withstand Capability)
• Programmable Voltage Range to Any PT ratio
• Supports: 3 phase 3 or 4 wires, 400/230V, 110/63V,208/120V
• Burden: 0.36VA per phase Max at 600V, 0.014VA at 120 Volts
• Input wire gauge max (AWG 12 / 2.5mmPPPP
Current Inputs
• Class : (0 to 5) A, 5 Amp Nominal
• Fault Current Withstand: 100 Amps for 10 Seconds, 300 Amps for 3 Seconds, 500 Amps for 1 Second.
• Programmable Current to Any CT Ratio
• Burden 0.005VA per phase Max at 11Amps
• 5mA Pickup Current • Pass through wire gauge dimension: 0.177" / 4.5mm
• Continuous current withstand: 20 amps for screw terminated or pass through current connections
Isolation
All Inputs and Outputs are galvanically isolated to 2500 Volts AC.
Environmental Rating Storage: (-25 to +70)° C Operating: (-10 to +65)° C Humidity: to 75% RH Non-Condensing Faceplate Rating: NEMA12 (Water Resistant) Environment : IP54 standard, IP65 optional Mounting Gasket Included
Sensing Method
• RMS
• Sampling at 120+ Samples per Cycle on all channels measured readings simultaneously
• Harmonic %THD (% of Total Harmonic Distortion)Update Rate
• Watts, VAr and VA-100msec
• All other parameters-1second
Power Supply Option D2:
• (65 to 275) Volts AC and (90 to 380) Volts DC. Universal AC/DC Supply Option D:
• 18-60VDC Burden: 10VA max.
Communication Format
• 2 Com Ports (Back and Face Plate)
• RS485 Port (Through Back Plate)
• 10/100 BaseT Ethernet Modbus TCP (INP10)
• Com Port Baud Rate: (1200 to 115200)
• Com Port Address: 0-247
• 8 Bit, No parity
• Modbus RTU Protocols
KYZ Pulse
• Type Form A
• On Resistance: 23-35 Ohm
• Peak Voltage: 350 VDC
• Continuous Load Current: 120 mA
• Peak Load Current: 350mA (10ms)
• Off Stat Leakage Current @ 350VDC: 1 mA
• Opto-Isolation: 3750V (6 0Hz, 1min)
Model | OB3000 |
---|---|
Manufacturer | Owen Brothers |
In Depth | Meter Accuracy • kWh Better than Class 1 per EN 62053-21 & BS 8431 • Kvarh Better than Class 2 per EN 62053-23 & BS 8431 • kW & kVA Better than Class 0.5 IEC 60688 • kvar Better than Class 0.5 IEC 60688 • Amps & Volts Class 0.2 IEC 60688 (0.01In – 1.2In or 0.1Un – 1.2Un) • PF ±0.2° (0.05In – 1.2In and 0.2Un – 1.2Un) • Neutral Current Class 0.5 IEC 60688 (0.05In – 1.2In) |
Length | 12 |
Height | 7 |
Bredth | 6 |
HS Tariff Code | HS8536901000 |
Packing Buffer (in percentage) | 10 |
Packing Type | Shared |